| Standard Name | Connection Type | Description | Approvals |
|---|---|---|---|
| RmTmpUnocHtgSpt | Software AV | Room Temperature Unoccupied Heating Setpoint | Stark Tech Approved |
| RmtOccOvr | Hardware AI | Remote Occupancy Override | Stark Tech Approved |
| RmtRmTmp | Hardware AI | Remote Room Temperature | Stark Tech Approved |
| RmtSATmp | Hardware AI | Remote Supply Air Temperature | Stark Tech Approved |
| RmtSpcTmp | Hardware AI | Remote Space Temperature | Stark Tech Approved |
| RmtTntOccOvr | Software DV | Remote Tenant Occupancy Override | Stark Tech Approved |
| Rm##UnocTmpSpt | Software AV | Room Unoccupied Temperature Setpoint | Stark Tech Approved |
| Rm##UnsfAlm## | Hardware DI | Room ## Unsafe Alarm | Stark Tech Approved |
| RmVacSts | Software DV | Room Vacancy Status (True = Room is Empty) | Stark Tech Approved |
| RmVntLoad | Software AV | Room Ventilation Load | Stark Tech Approved |
| RmVOC | Hardware AI | Room Volatile Organic Compounds | Stark Tech Approved |
| RotLdTS | Software DV | Rotate Lead Time Schedule | Stark Tech Approved |
| RotSw | Software DV | Rotate Switch | Stark Tech Approved |
| RPHWVlvPos | Hardware AO | Radiant Panel Hot Water Valve Position | Stark Tech Approved |
| RstCycActv | Software DV | Floating Actuator Reset Cycle Active | Stark Tech Approved |
| RstReqCyc | Software AV | Reset Request Hour Cycle Time | Stark Tech Approved |
| RstReqHLmt | Software AV | Reset Request Hour High Limit Setpoint | Stark Tech Approved |
| RTUEna | Software DV | Rooftop Unit Enable | Stark Tech Approved |
| SABalBoxFl | Software AV | Supply Air Balanced Box Rated Flow | Stark Tech Approved |
| SABalFlCorFct | Software AV | Supply Air Balanced Box Flow Correction Factor | Stark Tech Approved |
| SABalKFct | Software AV | Supply Air Balanced k-Factor | Stark Tech Approved |
| SABoxFlMax | Software AV | Supply Air Maximum Measured Box Flow | Stark Tech Approved |
| SABoxFlMid | Software AV | Supply Air Medium Measured Box Flow | Stark Tech Approved |
| SABoxFlMin | Software AV | Supply Air Minimum Measured Box Flow | Stark Tech Approved |
| SAClgTmpSpt | Software AV | Supply Air Cooling Temperature Setpoint | Stark Tech Approved |
Showing 25 of 4060 tags