Stark Tech Tags
| Standard Name | Connection Type | Description | Approvals | Report |
|---|---|---|---|---|
| CTBsnHtgRT | Software AV | Cooling Tower Basin Heating Run Time | Stark Tech Approved | |
| CTBsnHtgRTRst | Software DV | Cooling Tower Basin Heating Run Time Reset | Stark Tech Approved | |
| CTBsnHtgSts | Hardware DI | Cooling Tower Basin Heating Status | Stark Tech Approved | |
| CTBsnLvlAlmHiSpt | Software AV | Cooling Tower Basin Level High Alarm Setpoint | Stark Tech Approved | |
| CTBsnLvlAlmLoSpt | Software AV | Cooling Tower Basin Level Low Alarm Setpoint | Stark Tech Approved | |
| CTBsnSwpAlm | Hardware DI | Cooling Tower Basin Sweeper Alarm | Stark Tech Approved | |
| CTBsnSwpCmd | Hardware DO | Cooling Tower Basin Sweeper Command | Stark Tech Approved | |
| CTBsnSwpSts | Hardware DI | Cooling Tower Basin Sweeper Status | Stark Tech Approved | |
| CTBsnTmp | Hardware AI | Cooling Tower Basin Temperature | Stark Tech Approved | |
| CTBsnTmpAlm | Software DV | Cooling Tower Basin Temperature Alarm | Stark Tech Approved | |
| CTBsnTmpAlmLvl | Software DV | Cooling Tower Basin Temperature Alarm Level | Stark Tech Approved | |
| CTBsnTmpSpt | Software AV | Cooling Tower Basin Temperature Setpoint | Stark Tech Approved | |
| CTBsnTmpSptDif | Software AV | Cooling Tower Basin Temperature Setpoint Differential | Stark Tech Approved | |
| CTBypVlvCmd | Hardware DO | Cooling Tower Bypass Valve Command | Stark Tech Approved | |
| CTBypVlvESw | Hardware DI | Cooling Tower Bypass Valve End Switch | Stark Tech Approved | |
| CTBypVlvESwCls | Hardware DI | Cooling Tower Bypass Valve End Switch Closed | Stark Tech Approved | |
| CTBypVlvESwOpn | Hardware DI | Cooling Tower Bypass Valve End Switch Open | Stark Tech Approved | |
| CTBypVlvFbk | Hardware AI | Cooling Tower Bypass Valve Feedback | Stark Tech Approved | |
| CTBypVlvPos | Hardware AO | Cooling Tower Bypass Valve Position | Stark Tech Approved | |
| CT##BypVlvSts | Hardware DI | Cooling Tower Bypass Valve Status | Stark Tech Approved | |
| CTCentSeprAlm | Hardware DI | Cooling Tower Centrifugal Separator Alarm | Stark Tech Approved | |
| CTCentSeprCmd | Hardware DO | Cooling Tower Centrifugal Separator Command | Stark Tech Approved | |
| CTCentSeprSts | Hardware DI | Cooling Tower Centrifugal Separator Status | Stark Tech Approved | |
| CTCmd | Hardware DO | Cooling Tower Command | Stark Tech Approved | |
| CTCWRIsoVlvCmd | Hardware DO | Cooling Tower Condenser Water Return Isolation Valve Command | Stark Tech Approved |
Showing 25 of 4076 tags · Spotted a problem? Let us know