| Standard Name | Connection Type | Description | Approvals |
|---|---|---|---|
| CTRotSelfCor | Software DV | Cooling Tower Rotation Self Correcting Option | Stark Tech Approved |
| CTRotSelMd | Software MV | Cooling Tower Rotation Mode Select | Stark Tech Approved |
| CTRotSw | Software DV | Cooling Tower Rotation Switch | Stark Tech Approved |
| CTRotTSFrcRot | Software DV | Cooling Tower Rotation Time Schedule Force Rotation Option | Stark Tech Approved |
| CTRT | Software AV | Cooling Tower Run Time | Stark Tech Approved |
| CT##RTmp | Hardware AI | Cooling Tower Return Temperature | Stark Tech Approved |
| CTRTRst | Software DV | Cooling Tower Run Time Reset | Stark Tech Approved |
| CTSandFilAlm | Hardware DI | Cooling Tower Sand Filter Alarm | Stark Tech Approved |
| CTSandFilDifPr | Hardware AI | Cooling Tower Sand Filter Differential Pressure | Stark Tech Approved |
| CTSandFilSts | Hardware DI | Cooling Tower Sand Filter Status | Stark Tech Approved |
| CT##SmpTmp | Hardware AI | Cooling Tower Sump Temperature | Stark Tech Approved |
| CT##SmpTmpSpt | Software AV | Cooling Tower Sump Temperature Setpoint | Stark Tech Approved |
| CTSpyCmd | Hardware DO | Cooling Tower Spray Command | Stark Tech Approved |
| CTSpyOATmpLocSpt | Software AV | Cooling Tower Spray Operation Outside Air Temperature Lockout Setpoint | Stark Tech Approved |
| CTSpySts | Hardware DI | Cooling Tower Spray Status | Stark Tech Approved |
| CT##STmp | Hardware AI | Cooling Tower Supply Temperature | Stark Tech Approved |
| CTSts | Hardware DI | Cooling Tower Status | Stark Tech Approved |
| CTTmtSts | Hardware DI | Cooling Tower Water Treatment Status | Stark Tech Approved |
| CT##VibAlm | Hardware DI | Cooling Tower Vibration Alarm | Stark Tech Approved |
| CTXrt | Software AV | Cooling Tower Extended Run Time | Stark Tech Approved |
| CWApprSpt | Software AV | Condenser Water Approach Setpoint | Stark Tech Approved |
| CWBypVlvFAlm | Software DV | Condenser Water Bypass Valve Fail Alarm | Stark Tech Approved |
| CWBypVlvFAlmRst | Software DV | Condenser Water Bypass Valve Fail Alarm Reset | Stark Tech Approved |
| CWBypVlvFbk | Hardware AI | Condenser Water Bypass Valve Feedback | Stark Tech Approved |
| CWBypVlvPos | Hardware AO | Condenser Water Bypass Valve Position | Stark Tech Approved |