Stark Tech Tags
| Standard Name | Connection Type | Description | Approvals |
|---|---|---|---|
| OccCmdRT | Software AV | Occupancy Command Run Time | Stark Tech Approved |
| OccMd | Software MV | Occupancy Mode | Stark Tech Approved |
| OccMdSts | Software MV | Occupancy Status | Stark Tech Approved |
| OccOvr | Hardware DI | Occupancy Override | Stark Tech Approved |
| OccOvrTmL | Software AV | Occupancy Override Time Left | Stark Tech Approved |
| OccSig | Hardware DI | Occupancy Signal | Stark Tech Approved |
| OccSnsr | Hardware DI | Occupancy Sensor | Stark Tech Approved |
| OccSnsrDlyOf | Software AV | Occupancy Sensor Delay Off | Stark Tech Approved |
| OccSnsrEna | Software DV | Occupancy Sensor Enable | Stark Tech Approved |
| OccSnsrSts | Hardware DI | Occupancy Sensor Status | Stark Tech Approved |
| OccSrcMd | Software MV | Occupancy Source | Stark Tech Approved |
| OperMdSts | Software MV | Operation Status | Stark Tech Approved |
| OperStsCnt | Software AV | Operation Status Count | Stark Tech Approved |
| OpMd | Software MV | Operating Mode | Stark Tech Approved |
| OptStrtClgEna | Software DV | Optimal Start Cooling Enable | Stark Tech Approved |
| OptStrtClgMaxTm | Software AV | Optimal Start Cooling Maximum Time | Stark Tech Approved |
| OptStrtClgRT | Software AV | Optimal Start Cooling Run Time | Stark Tech Approved |
| OptStrtHtgEna | Software DV | Optimal Start Heating Enable | Stark Tech Approved |
| OptStrtHtgMaxTm | Software AV | Optimal Start Heating Maximum Time | Stark Tech Approved |
| OptStrtHtgRT | Software AV | Optimal Start Heating Run Time | Stark Tech Approved |
| OvrAlm | Hardware DI | Override Alarm | Stark Tech Approved |
| OvrTm | Software AV | Override Time | Stark Tech Approved |
| OvrTmh | Software MV | Occupancy Override Timer in Hours | Stark Tech Approved |
| P#Alm | Hardware DI | Pump Alarm | Stark Tech Approved |
| P#Amp | Hardware AI | Pump Amps | Stark Tech Approved |
Showing 25 of 4060 tags